Gas Detection (H2S and Methane)

Drilling Equipment Inspections

How often
Calibrate and test when the BOP stack is first installed after rig-up, at every AOGCC-witnessed BOP test, and at least every 30 days. A system that self-checks continuously is function-tested at those times and at least every 6 months. PM Plan: H2S and methane detectors Category II weekly (Electrician); portable monitors monthly.
Source: 20 AAC 25.066(b); Nordic PM Plan 9.0 Table 2 and Table 5; Nordic PM Plan 5.0 Table 2
📋 Inspection Information
📏 Readings
✅ Checklist

Answer every line. N/A means it does not apply today. Every Fail needs a note saying what is wrong.

Sensor locations (AOGCC minimum)
Methane: under the substructure near the cellar, over the shaker, and above the floor near the driller; also over the pits if they are remote from the shaker and enclosed
Source: 20 AAC 25.066(a)(1)
Methane sensors placed to catch a lighter-than-air gas (high)
Source: 20 AAC 25.066(a)(2)
H2S: under the substructure near the cellar, near the shaker, and above the floor near the driller
Source: 20 AAC 25.066(a)(3)
H2S sensors placed to catch a heavier-than-air gas (low)
Source: 20 AAC 25.066(a)(4)
All Rig 4 sensor heads in service (Start-Up lists 6)
Source: Nordic R4 Rig Start-Up 14.0 step 6
Alarms
Sensors automatic, working independently and in parallel, sampling at least every minute
Source: 20 AAC 25.066(a)(5)
Separate alarms: visual for the low level, audible for the high level
Source: 20 AAC 25.066(a)(6)
Alarms seen and heard at the driller's station
Source: 20 AAC 25.066(a)(9)
H2S alarm heard throughout the location, including camp buildings
Source: 20 AAC 25.066(a)(9)
Methane low alarm set at no more than 20% LEL; high at no more than 40% LEL
Source: 20 AAC 25.066(a)(7)
H2S low alarm set at 10 ppm; high at no more than 20 ppm
Source: 20 AAC 25.066(a)(8)
Testing and records
Calibrated and tested within the required interval; record kept at the rig
Source: 20 AAC 25.066(b)
Gas alarms tested before the first BOP test after start-up
Source: Nordic R4 Rig Start-Up 26.0 item 21
Any gas detection failure reported to AOGCC within 24 hours
Source: 20 AAC 25.066(c)
Portable gas monitors: monthly check done; bump test and calibration per the manufacturer
Source: Nordic PM Plan 9.0 Table 5; manufacturer instructions
Personal H2S monitors in service less than 2 years
Source: Nordic PM Plan 9.0 Table 5
📝 Findings & Actions